Showing posts with label Technology Research. Show all posts
Showing posts with label Technology Research. Show all posts

Thursday, November 15, 2018

TRC Southwire 24646-001 30 Amp ELCI/GFCI

Sords Electric Sells the TRC HD-PRO ELCI 24646-001-1


The Technology Research HD Pro 24646 High Power ELCI is designed for Motors, pumps, welders, pressure washers, hoists and other high power devices that need GFCI/ELCI protection. The HD Pro 24646 can be configured for inline or bulk head mounting.

Click Link below to order:
TRC HD-PRO 24646-001 30 AMP Adjustable (6/10/30 mA) GFCI / ELCI, 480/3 VAC

The Southwire TRC HDPro 24646-001 has 2 feet of cable on both the line side and the load side. When the mA trip leakage point is reached the unit will trip and require a MANUAL reset.  If the primary power is disrupted the 24646 will reset automatically when power is restored or returns to normal.

Southwire TRC 30 Amp  HD-Pro 24646-001 GFCI ELCI




















The TRC HD-Pro Features 

480 volts - Three Phase
30 Amps
4/4 AWG Cord Gauge
Adjustable Trip levels are 6mA, 10mA and 30mA

24646-001 HD-Pro GFCI/ELCI Technical Data

Response Time: 25mS
Frequency: 50/60 Hz
Endurance: 3,000 operations minimum
Overload Current: 6 times rated Current (30 Amps)
Ambient Temperature: -20ºC to +40ºC
Insulation Voltage: 1500 VRMS - 1 minute
Power On Indication: Lighted Indicator
Drop Out Voltage: 60% Rated Voltage (480 v)
Reset Type: Automatic (When primary Power is lost)
Connection Type: Flying Leads
NEMA 4 Polymer

See Specifications Sheet HERE!

To be called a GFCI (Ground Fault Circuit Interruptor) the unit needs to trip no higher than 6mA.  Above that the unit becomes an ELCI (Equipment Leakage Circuit Interruptor).

A Ground-fault occurs when there is a break in the low resistance grounding path from a tool or electrical system. The electrical current may then take an alternative path to the ground through the user, resulting in serious injury or death.  The ground-fault circuit interrupter, or GFCI, is a fas acting circuit breaker designed to shut of electric power in the event of a ground fault within as little as 1/40 of a second. It works by comparing the amount of current going to and returning from the equipment along the circuit conductors. When the amount going differs from the amour retuning by approximately 5 milliamperes (4-6mA), the GFCI trips/interrupts the current.

The GFCI is rated to trip quickly enough to prevent an electrical incident.  If it is properly installed and maintained, this will happen as soon as the faulty tool is plugged in.  If the grounding conductor is not intact or of low impedance the GFCI may not trip until a person provides a path.  In this case, the person will receive a shock, but the GFCI should trip so quickly that the shock will not be harmful. The most common type of shock is from the Ground Fault. GFCIs also protect against fires, overheating and wire destruction.

TRC HD-PRO 24646-001 30 AMP Adjustable (6/10/30 mA) GFCI / ELCI, 480/3 VAC

Southwire HD-PRO 24646 GFCI from TRC - 30 amps, 480 volts





















Sords Electric
216-765-4233
www.sordselectric.com


Una pérdida a tierra ocurre cuando hay una ruptura en el camino de resistencia baja para conexión a tierra de una herramienta o un sistema eléctrico. La corriente eléctrica entonces puede tomar una trayectoria alterna a la tierra a través del trabajador, resultando en lesiones serias o la muerte.
El interruptor para circuitos con pérdida a tierra, o GFCI, es un circuito interruptor de energía de acción rápida diseñado para desconectar la energía eléctrica en caso de una pérdida a tierra en un lapso de 140 de segundo. Esto funciona comparando la cantidad de corriente que sale y que regresa del equipo a lo largo de los conductores de circuito. Cuando la cantidad que sale es diferente de la cantidad que regresa por aproximadamente 5 mili-amperios, el GFCI interrumpe la corriente.
El GFCI está clasificado para desconectar la corriente suficientemente rápido para prevenir un incidente eléctrico. Si es instalado y mantenido correctamente, esto pasará tan pronto como el equipo defectuoso es enchufado. Si el conductor de conexión a tierra no está intacto o es de baja impedancia, el GFCI quizás no funcione hasta que una persona le proporcione una trayectoria. En este caso, la persona recibirá una descarga, pero el GFCI debe activarse tan rápidamente que la descarga no sería mortal o dañina.
216-765-4233
www.sordselectric.com

Technology Research Corporation - Southwire 

TRC HD-PRO GFCI ELCI 24646-001 30 amps 480/3/60 volts

Sunday, October 6, 2013

High Power GFCI by TRC and Southwire


Technology Research High Power HD-Pro Ground Fault Interrupters from Sords Electric


TRC HD-Pro Southwire High Power GFCI/ELCI Ground Fault 







With the  TRC HD-PRO Series heavy duty, high power ground fault interrupters (GFCIs) you can feel safe around electrical equipment used in wet environments.  Single and three phase models are available for pumps, motors, welders, pressure washers, portable conveyers, hoists, mining tools and a host of high powered machinery.  All HD-PRO models automatically reset after interruption and restoration of power, but will trip on detection of hazardous ground fault conditions.
TRC Hd-Pro GFCI's are available in 120V, 30A to 600V, 100A.
TRC engineered HD-PRO models with an adjustable trip level selector, HD-PRO 6.10.30 and HD-PRO 10.30.50.  This unique design allows the flexibility to select and lock in a trip level of 6, 10 or 30mA, or 10, 30 or 50mA, customizing each model for the specific type of equipment to maximize protection while avoiding unwanted tripping.


































TRC engineers designed the HD-PRO models specifically for high current, rugged environments and these models are field-proven in all kinds of tough applications. The entire HD-PRO family (120V/30A to 600V/80A) is designed to trip within 25 milliseconds after ground fault detection at an adjustable selected trip level of 6, 10 or 30 mA.
Before the development of the HD-PRO Series, facilities with high current – high voltage equipment or three phase systems employed expensive ground fault breakers at the source of the branch circuit, or went without ground fault protection, leaving personnel and equipment unprotected.
Circuit breakers can withstand high current levels but have short mechanical lives and were not designed for switching duty. Localized ground faults, with circuit breakers, either shut down the whole branch circuit or were overloaded because the available devices were not portable and were often too costly.
The HD-PRO Series utilizes contactors that are fully rated for motor switching demands. In addition to being far less expensive than three phase breakers, the HD-PRO models protect expensive high current – high voltage equipment at the point of use while offering substantial shock protection for personnel.
TRC is an internationally recognized leader in electrical safety products that protect equipment, prevent electrical fires and protect against electrocution and serious injury from electrical shock.

High Power/ Heavy Duty GFCI's and ELCI's protect Motors, Pumps, Welders, Portable Conveyors, Freight Lifts, Pressure Washers

Heavy Duty - High Power ELCIs - 30A and 60A

Configured for both in-line and bulk head mount. Engineered to trip within 25 milliseconds. 
The TRC 24140 and 24500 have 2’ of cable on both line and load side. Will remain reset on power restoration following disruption of primary power.

24140 002 ELCI Volts/Amps: 240V/30A Cord Gauge: 10/4 AWG Trip Level: 10 mA Single Phase NEMA 4 Housing

24500 006 ELCI Volts/Amps: 208-240V/30A Cord Gauge: 10/4 AWG Trip Level: 10 mA Three Phase NEMA 4 Housing 


Configured for both in-line and bulk head mount. Engineered to trip within 25 milliseconds.  NEMA 4 polymer Enclosure
The TRC 24520, 24530 and 25560 have 2’ of cable on both line and load side. To prevent equipment startup after ELCI trips, manual reset required. Will reset on power restoration following disruption of primary power.

24520 001  Volts/Amps: 120V/60A  Cord Gauge: 4/3 AWG  Trip Level: 10 mA  Single Phase

24530 001  Volts/Amps: 240V/60A  Cord Gauge: 4/4 AWG  Trip Level: 10 mA  Three Phase

25560 001  Volts/Amps: 380V/60A  Cord Gauge: 4/4 AWG  Trip Level: 30 mA  Three Phase


Configured for both in-line and bulk head mount. Engineered to trip within 25 milliseconds.  NEMA 4 polymer Enclosure
The TRC 24396, 24542, 24646, 24672 and 24846 have 2’ of cable on both line and load side. To prevent equipment startup after GFCI/ELCI trips, manual reset required. Will reset on power restoration following disruption of primary power. 6.10.30TM key enables trip level selection and locking at a trip level with key removal.

24396 001 Volts/Amps: 277V/30A Cord Gauge: 10/3 AWG TripLevel:6,10 & 30 mA Single Phase

24542 001 Volts/Amps: 208-240V/60A  Cord Gauge: 4/4 AWG  TripLevel:6,10 & 30 mA  Three Phase

24646 001 Volts/Amps: 480V/30A Cord Gauge: 10/4 AWG TripLevel:6,10 & 30 mA Three Phase

24672 001 Volts/Amps: 480V/60A  Cord Gauge: 4/4 AWG  TripLevel:6,10 &30 mA  Three Phase

24846 001 Volts/Amps: 208-240V/30A  Cord Gauge: 8/5 AWG  TripLevel:6,10 & 30 mA  Three Phase


Configured for both in-line and bulk head mount. Engineered to trip within 25 milliseconds.  NEMA 4 polymer Enclosure
The TRC 24396, 24542, 24646, 24672 and 24846 have 2’ of cable on both line and load side. To prevent equipment startup after GFCI/ELCI trips, manual reset required. Will reset on power restoration following disruption of primary power. 6.10.30TM key enables trip level selection and locking at a trip level with key removal.

24736 001 Volts/Amps: 480V/100A  Cord Gauge: 2/4 AWG  TripLevel:6,10 & 30 mA  Three Phase

24786 001  Volts/Amps: 208-240V/80A  Cord Gauge: 4/4 AWG  TripLevel:6,10 & 30 mA  Three Phase

24796 001  Volts/Amps: 480V/80A  Cord Gauge: 4/4 AWG  TripLevel:6,10 & 30 mA  Three Phase

24946 003  Volts/Amps: 600V/60A  Cord Gauge: 4/4 AWG  TripLevel:6,10 & 30 mA  Three Phase

24992 001  Volts/Amps: 600V/80A  Cord Gauge: 4/4 AWG  TripLevel:6,10 & 30 mA  Three Phase

24994 001  Volts/Amps: 600V/100A  Cord Gauge: 2/4 AWG  TripLevel:6,10 & 30 mA  Three Phase


















Configured for both in-line and bulk head mount. Engineered to trip within 25 milliseconds.  NEMA 4 16 gauge steel enclosure.
To prevent equipment startup after EGFPD or GFCI/ELCI trips, manual reset required. Will reset on power restoration following disruption of primary power. 
Key enables trip level selection and locks at a trip level with key removal.

For the below units, please call Sords Electric or use our Parts Form Request to receive a quotation

44110 012  EGFPD (Equipment Ground Fault Protection Devices)  CSA Listed
Volts/Amps: 208-240V/30A TripLevel:10,30 & 50 mA  Three Phase

44140 012  EGFPD (Equipment Ground Fault Protection Devices)  CSA Listed
Volts/Amps: 208-240V/60A TripLevel:10,30 & 50 mA  Three Phase

44120 012 EGFPD (Equipment Ground Fault Protection Devices)  CSA Listed
Volts/Amps: 480V/30A TripLevel:10,30 & 50 mA  Three Phase

44130 012 EGFPD (Equipment Ground Fault Protection Devices)  CSA Listed
Volts/Amps: 480V/60A TripLevel:10,30 & 50 mA  Three Phase

44610 001  GFCI / ELCI 
Volts/Amps: 208-240V/30A TripLevel:10,30 & 30 mA  Three Phase

44640 001  GFCI / ELCI 
Volts/Amps: 208-240V/60A TripLevel:10,30 & 30 mA  Three Phase

44620 001 GFCI / ELCI 
Volts/Amps: 480V/30A TripLevel:10,30 & 30 mA  Three Phase

44630 001 GFCI / ELCI 
Volts/Amps: 480V/60A TripLevel:10,30 & 30 mA  Three Phase

Why use Ground Fault:

A “Ground Fault” is a dangerous electrical condition where current flows unintentionally between a live conductor and ground. A severe or fatal electric shock can occur when a user touches the pressure washer if the machine is ungrounded. This could happen if the power cord to extension cord connections become wet or a fault exists within the pressure washer’s sophisticated electrical system. GFCI’s prevent possible electrocution and equipment damage due to electrical malfunction. Once the GFCI trips, the power is interrupted, stopping the pressure washer power and making it electrically safe for people and preventing costly equipment damage.

Avoiding electrical accidents and equipment damage are keys to reducing liability and increasing productivity. Minimum ground fault, GFCI, protection can be incorporated into the main power disconnect device and could be considered adequate for the entire system. However, in such a design, any downstream ground fault could trip the main protective device resulting in a complete substation power outage. The NEC's purpose, in its own words, is "the practical safeguarding of persons and property…but not necessarily efficient, convenient, or …for good service…" (Article 90.1A, B). In other words, system reliability is left to common sense and good engineering design practices. For this reason ground fault, GFCI, protection of the circuit may be highly desirable and recommended for reliable and continuous operation.
Technology Research Corporation (TRC) is a leading manufacturer of electrical safety products. Based in Clearwater, Florida, TRC designs, develops and manufactures products that prevent electrical fires and protect people and pets from electrocution and serious injury caused by electrical shock.
Use Our TRC parts form as a REQUEST for QUOTE.
800-929-2845
info@sordselectric.com

Friday, April 27, 2012

TRC Drag Strip Connector Protector

The TRC ( Coleman Cable ) Drag Strip allows connection of extension cords in a water proof method as well as keeping the cords from separating.

Fits most 15 and 20 Amp molded plugs and connectors.  It installs in just minutes without the use of any tools.  Ideal for use with power tools, lawn and garden equipment or any extension cord application.  Protection from rain, mud, dust, surface water and ultra violet rays.



  • Eliminates frustrating power supply interruptions
  • Prevents cords from separating at plug and receptacle
  • Weather-tight seal protects against harsh conditions
  • Installs easily in less than a minute




216-765-4230




Friday, July 9, 2010

OSHA Rule Expands Requirements for GFCI Use


OSHA Rule Expands Requirements for GFCI Use
Buy at Sords Electric


Are you compliant?
An important change in OSHA Regulations in 2007 has broadened
the requirements for using portable GFCI’s inmost industries.



OverviewMandatory use of portable Ground Fault Circuit Interrupters (GFCI’s) began in the 1970’s not long after the Occupational Safety and Health Administration (OSHA) was formed by an Act of
Congress. The first requirements for GFCI use resulted from an OSHA mandate applying to
Construction Industry businesses. The mandate required the use of GFCI’s whenever
“temporary power”was used on the jobsite. The resulting use of GFCI’s in construction work has saved many workers’lives in the intervening years since the mandate was issued.
Capitalizing on the Construction Industry safety benefits realized, new regulations which went into effect in August, 2007 extended GFCI-use requirements for the first time to OSHA’s General Industry category of businesses which cover most of the rest of U.S. industry with the exception of agriculture, mining and maritime. Now, in order to comply with OSHA Regulations, a great deal of maintenance, remodeling or repair activities, involving buildings, structures or equipment must be done with workers using GFCI protected equipment.
The new activities for which OSHA has mandated the use of GFCI’s cover a large segment of industrial functions having“construction-like” characteristics such as are found in MRO, facilities engineering and disaster preparedness and recovery disciplines. Industries covered include
product and materials manufacturing, automotive manufacturing, breweries and bottling plants, chemical and petrochemical processing, food processing and many others.
Previously, most portable GFCI extension cords, quad boxes and other ground fault
protection equipment have been bought by construction and electrical contractors.
Distributors will now find many new opportunities for GFCI sales with their industrial customers.

BACKGROUND

OSHA’s scope of regulation covers three major business areas; the Construction Industry, the Maritime Industry and a third category, General Industry, which covers most other business enterprises except for those in mining and agriculture which are overseen by other government
agencies. OSHA’s regulations are Federal Law and are contained in the U.S. Government’s Code of Federal Regulations (CFR). Violations of OSHA regulations can subject companies to legal action and fines.
Prior to the most recent update, OSHA's General Industry electrical regulations (29CFR1910, Subpart S) were last updated in August 1990 and were based on Part I of the National Fire Protection Association’s NFPA 70E Standard entitled Electrical Safety Requirements for EmployeeWorkplaces (1988 Edition). OSHA’s Construction Industry electrical regulations (29CFR1926, Subpart K) were last updated in 1986. NFPA 70E provides practical application to
OSHA requirements. Numerous enhancements in technology have occurred since these regulations were last revised.
In an effort to bring its regulations up to date, OSHA published new General Industry regulations in 2007 based on Part I of the 2000 Edition of NFPA 70E. In doing so, and in response to requests from industry stakeholders, OSHA has provided General Industry companies with new rules that reflect more current versions of NFPA 70E and the National
Electrical Code (NEC). In fact, until they are updated in the future, the General Industry rules regarding GFCIs are now more up-to-date than those for the Construction Industry.


Regulations


Set forth below are the actual citations from OSHA’s General Industry regulations that were issued in 2007. Keep in mind that prior to the issuance of these new regulations, OSHA did not require the use of GFCIs for construction-like work performed by General Industry companies.


From29CFR1910, Subpart S, Article 1910.304(b)(3)
Ground-fault circuit interrupter protection for personnel.

1910.304(b)(3)(i)
All 125 Volt, single-phase, 15 and 20 Ampere receptacles installed in bathrooms or on rooftops shall have ground fault circuit interrupter protection for personnel.

1910.304(b)(3)(ii)
The following requirements apply to temporary wiring installations that are used during construction-like activities, including certain maintenance, remodeling, or repair activities involving buildings, structures or equipment.

1910.304(b)(3)(ii)(A)
All 125 Volt, single-phase, 15, 20, and 30 Ampere receptacle outlets that are not part of the permanent wiring of the building or structure and that are in use by personnel shall have ground fault circuit interrupter protection for personnel.
Note 1 to paragraph (b)(3)(ii)(A) of this section: A cord connector on an extension cord set is considered to be a receptacle outlet if the cord set is used for temporary electric power.
Note 2 to paragraph (b)(3)(ii)(A) of this section: Cord sets and devices incorporating the required ground fault circuit interrupter that are connected to the receptacle closest to the source of power are acceptable forms of protection.

1910.304(b)(3)(ii)(B)
Receptacles other than 125 Volt, single-phase, 15, 20, and 30 Ampere receptacles that are not part of the permanent wiring of the building or structure and that are in use by personnel shall have ground fault circuit interrupter protection for personnel.  (Extension cords with Ground Fault built in.)

1910.304(b)(3)(ii)(C)
Where the ground fault circuit interrupter protection required by paragraph (b)(3)(ii)(B) of this section is not available for receptacles other than 125 Volt, single-phase, 15, 20, and 30 Ampere, the employer shall establish and implement an assured equipment grounding conductor program covering cord sets, receptacles that are not a part of the building or structure, and equipment connected by cord and plug that are available for use or used by employees on those receptacles.


TRC is an internationally recognized leader in electrical safety products that protect equipment, prevent electrical fires and protect against electrocution and serious injury from electrical shock.

Sords Electric sells TRC products.

800 929-2845

Saturday, May 16, 2009

GFCI ~ manual reset vs. automatic reset

trc gfci 30 amp
Ground Fault Circuit Interrupter or a GFCI is a switch designed to protect people from electrical shocks and electrocution.  The GFCI monitors the current flow into and out of an appliance or circuit and if the current is not equal, the GFCI will switch or trip in milliseconds.  After a trip the GFCI needs to be reset by pushing the "reset" button on the GFCI.  GFIC's are  required in homes in the bathrooms, kitchens and laundry rooms.  

A GFCI can come in wither manual reset mode or automatic reset models.  In this discussion regarding auto vs. manual reset is not after a GFCI trips due to a fault, but when the GFCI's circuit loses power or is initially powered up or plugged in.  GFCI's in homes that are wired into the wall are all AUTO reset GFCI's.  The GFCI after a power outage will reset itself with an electrical coil so that it is "ready" to go.  An auto reset GFCI should always be used for indoor use when the load is not a dangerous.  

A manual reset GFCI is usually used for outdoor power equipment or on the job site electrical tools and applications.The manual reset GFCI will need to be "reset" when the GFCI is plugged in or when power is applied to the curcuit.  The GFCI will trip when power is removed from the circuit or unplugged.  The GFCI will also trip when a fault is detected.  In both cases the GFCI will need to be manually reset.  Most of the GFCI's that we sell are manual reset GFCI's.




Thursday, May 14, 2009

GFCI ~ Ground Fault Circuit Interrupter

A "GFCI" is a ground fault circuit interrupter. A ground fault circuit interrupter is an inexpensive electrical device that, if installed in household branch circuits, could prevent over two-thirds of the approximately 300 electrocutions still occurring each year in and around the home. Installation of the device could also prevent thousands of burn and electric shock injuries each year.

The GFCI is designed to protect people from severe or fatal electric shocks Because a GFCI detects ground faults, it can also prevent some electrical fires and reduce the severity of others by interrupting the flow of electric current.

In the home's or other building's wiring system, the GFCI constantly monitors electricity flowing in a circuit, to sense any loss of current. If the current flowing through the circuit differs by a small amount from that returning, the GFCI quickly switches off power to that circuit. The GFCI interrupts power faster than a blink of an eye to prevent a lethal dose of electricity. You may receive a painful shock, but you should not be electrocuted or receive a serious shock injury.

In homes built to comply with the National Electrical Code (the Code), GFCI protection is required for most outdoor receptacles (since 1973), bathroom receptacle circuits (since 1975), garage wall outlets (since 1978), kitchen receptacles (since 1987), and all receptacles in crawl spaces and unfinished basements (since 1990).

Owners of homes that do not have GFCls installed in all those critical areas specified in the latest version of the Code should consider having them installed. For broad protection, GFCI circuit breakers may be added in many panels of older homes to replace ordinary circuit breaker. For homes protected by fuses, you are limited to receptacle or portable-type GFCIs and these may be installed in areas of greatest exposure, such as the bathroom, kitchen, basement, garage, and outdoor circuits.

A GFCI should be used whenever operating electrically powered garden equipment (mower, hedge trimmer, edger, etc.). Consumers can obtain similar protection by using GFCIs with electric tools (drills, saws, sanders, etc.) for do-it-yourself work in and around the house.

Circuit breaker and receptacle-type GFCIs may be installed in your home by a qualified electrician. Receptacle-type GFCIs may be installed by knowledgeable consumers familiar with electrical wiring practices who also follow the instructions accompanying the device. When in doubt about the proper procedure, contact a qualified electrician. Do not attempt to install it yourself.

The portable GFCI requires no special knowledge or equipment to install.

All GFCIs should be tested once a month to make sure they are working properly and are protecting you from fatal shock. GFCIs should be tested after installation to make sure they are working properly and protecting the circuit.

To test the receptacle GFCI, first plug a nightlight or lamp into the outlet. The light should be on Then, press the "TEST" button on the GFCI. The GFCI's "RESET" button should pop out, and the light should go out.

If the "RESET" button pops out but the light does not go out, the GFCI has been improperly wired. Contact an electrician to correct the wiring errors.

If the "RESET" button does not pop out, the GFCI is defective and should be replaced. 

If the GFCI is functioning properly, and the lamp goes out, press the "RESET" button to restore power to the outlet.

GFCI's should be used in Commercial and industrial enviroments as well.  NEC code requires the use of GFCI's with all portable electrical tools, that need to be plugged in, within a plant or on a job site.

Related products for commercial properties and job sites are our cable mats.