Monday, June 8, 2009

Watlow DIN-A-MITE A Power Controller

SORDS ELECTRIC sells the Watlow DIN-A-MITE Power Controllers


The Watlow® DIN-A-MITE® Style A power controller provides 

a low-cost, highly compact and versatile solid state option 

for controlling electric heat. You also get all the quality you 

expect from a Watlow designed and manufactured product. 

DIN-rail and back panel mounting is standard on every 

controller. There is no need to worry about mercury, the 

DIN-A-MITE controller is mercury free. 

Capabilities include single-phase zero cross switching up 

to 25 amperes at 600VÅ(ac) (see rating curve). A unique 

integrated design removes the guesswork associated with 

selecting a proper heat sink and adequate terminations for 

the application. 

Variable time base, 4-20mA process control or Vı(ac/dc) 

input contactor versions are available. All configurations 

are model number dependent and factory selectable. This 

power controller also includes 200KA short circuit current 

rating (SCCR) tested up to 480VÅ(ac) to prevent arch flash 

with required fusing. 


The DIN-A-MITE power controller is made in the 

United States. 



Features and Benefits 

200KA Short Circuit Current Rating (SCCR) 

Prevents arc flash 

DIN-rail or standard panel mount 

Provides versatility, quickness and low-cost 

installation 

Compact size 

Reduces panel space; less cost 

Touch-safe terminals 

Increases safety for installer/user 

No mercury 

Assures environmental safety 

Faster switching with solid state 

Saves energy and extends heater life 

UL® 508 listed, C-UL® and CE with filter 

Meets applications requiring agency approval 


Specifications 

Operator Interface 

• Command signal input 

• Input indicator light LED 

Amperage 

• Single phase, see the output rating curve 

• Max. I2t for fusing: 4000A2sec 

• Latching current: 200mA 

• Holding current: 100mA 

• Power dissipation is 1.2 watts per amperes switched 

• 200KA SCCR, Type 1 and 2 approved with the recommended 

fusing; see user manual. 

Line Voltage 

• 20 to 660V~(ac) model number dependent; see ordering 

information 

• Off-state leakage: 1mA at 77°F (25°C) max. 

• 50/60Hz independent 

Control Mode-Zero Cross 

• Input control signal Type C: VÎ(dc) input contactor 

• Input control signal Type K: V~(ac) input contactor 

• To increase service life on contactor input models, the cycle time 

should be less than three seconds 

• Input Control Signal Type F: 4 to 20mAÎ(dc) proportional variable 

time base control; 3 cycles on, 3 cycles off at 50% power 

Input Command Signal 

• AC contactor 

24VÅ(ac) ±10%, 120VÅ(ac) +10/-25%, 240VÅ(ac) +10/-25% @ 

25mA max. per controlled leg 

• DC Contactor 

4.5VÎ to 32VÎ(dc): max. current @ 4.5 VÎ(dc) is 8mA 

per leg 

• Loop powered linear current 

4mAÎ to 20mAÎ(dc): loop-powered, input Type F0 option only 

(requires current source with 6.2VÎ(dc) available, no more than 

three DIN-A-MITE inputs can be connected in series) 

Agency Approvals 

• CE with proper filter: 

204/108/EC Electromagnetic Compatibility Directive 

EN 61326-1: Industrial Immunity Class A Emissions 

2006/95/EC Low Voltage Directive 

EN 50178 Safety Requirements 

Installation category III, pollution degree 2 

• UL® 508 listed and C-UL® File E73741 

Input Terminals 

• Compression: will accept 0.2 to 2 mm2 (24 to 14 AWG) wire 

Line and Load Terminals 

• Compression: will accept 0.8 to 8.4 mm2 (18 to 8 AWG) wire 

Operating Environment 

• Up to 176°F (80°C); see the output rating curve chart for your 

application 

• 0 to 90% RH (relative humidity), non-condensing 

• Installation only tested to 3,000 meters 

• Units are suitable for “Pollution degree 2” 

Mounting 

Options include DIN-rail or standard back panel mounting 

• The DIN-rail specification is: DIN EN 50022, 35 mm by 7.5 mm 

• Mount the cooling fins vertically 

Dimensions 

• Height: 3.7 in. (95 mm) high x 1.8 in. (45 mm) wide x 

3.9 in. (98 mm) deep 

• Weight: 0.71 lb (0.32kg) 


Ordering Information 

To order, complete the code number on the right with the 

information below. 

DIN-A-MITE Style A = Solid State Power Controller 

DA10 - __ __ __ __ - 0 __ __ __ 

Phase 

1 = 1-phase, 1 controlled leg 

Cooling and Current Rating 

0 = Natural convection current 

rating 18A @ 50˚C (see 

derating curve for current rating 

at other temperatures) 

Line and Load Voltage 

02 = 24 to 48VÅ(ac) 

24 = 100 to 240VÅ(ac) 

60 = 277 to 600VÅ(ac) 

Input Type 

C0 = 4.5 to 32VÎ(dc) contactor 

F0 = 4 to 20mAÎ(dc) proportional 

K1 = 22 to 26VÅ(ac) contactor 

K2 = 100 to 120VÅ(ac) contactor 

K3 = 200 to 240VÅ(ac) contactor 

Manual Language 

0 = English 

1 = German 

2 = Spanish 

3 = French 

Custom Parts Designation 

00 = Standard parts 

Recommended Semiconductor Fuse and Fuse Holder 

Watlow Cooper Bussmann® Ferraz Shawmut 

Fuse 17-8025 FWC25A10F L330014 

Holder 17-5110 B24202 G81219 



No comments: